Default Fixture Wattage Reference Table

This table is to be used as a reference for determining the wattage of baseline (existing) fixtures for the ComEd Energy Efficiency Program. Wattages for all new (proposed) fixtures should be referenced from the new product specifications.

There are many factors that affect the input wattage of a fixture: ballast factor, lamp quality, system voltage, etc. The more information that is provided about your project, the more accurate the incentive and energy savings calculations can be. If there is any doubt as to which fixture type is correct, the conservative wattage will be used. To ensure that the wattages used in incentive calculations are as accurate as possible, pictures are recommended for all of the fixture types listed below in red marked *.

This table is made up of the most common fixtures but does not include all fixture types. T12 fixtures are listed with energy-saving (ES) magnetic ballasts and standard magnetic ballasts. If a fixture type is not listed on this table, it does not necessarily mean that the fixture is not eligible for an incentive. Please visit ComEd.com/BizIncentives or call us at 855-433-2700 if you have any questions.

T12
Number of Lamps Per Fixture 2-FT 20W Lamps 3-FT 30W Lamps 4-FT 34W U-Lamps 4-FT 40W U-Lamp(s) with ES Magnetic Ballasts (Standard Magnetic Ballasts) 4-FT 34W Lamp(s) with ES Magnetic Ballast 4-FT 34W Lamp(s) with Standard Magnetic Ballast 4-FT 40W Lamp(s) with ES Magnetic Ballast 4-FT 40W Lamp(s) with Standard Magnetic Ballast
1 28 37 43   40 50* 48* 57*
2 56 74 72 85 (96)* 68 80* 82* 94*
3 62 111 115   110 130* 122* 147*
4 112 148     139 160* 164* 182*
6 146       216 236* 258* 282*
8         288      
T12 8-FT
Number of Lamps Per Fixture 60W Lamp(s) with ES Magnetic Ballast 60W Lamp(s) with Standard Magnetic Ballast 75W Lamp(s) with ES Magnetic Ballast 75W Lamp(s) with Standard Magnetic Ballast HO 95W Lamp(s) with ES Magnetic Ballast (Standard) HO 110W Lamp(s) with ES Magnetic Ballast (Standard) VHO 185W Lamp(s) with Magnetic Ballast T12 VHO 215W Lamp(s) with Magnetic Ballast
1 62 75 91* 100* 104 (112)* 132 (145)* 205* 230*
2 123 128 158* 173* 207 (227)* 237 (257)* 380* 450*
3 203 210   237* 311 (380)* 369 (392)* 585* 680*
4 246 256 316* 346* 414 (454)* 474 (514)* 760* 900*
T8
Number of Lamps Per Fixture 2-FT 17W Lamps 3-FT 25W Lamps 4-FT 32W U-Lamps 4-FT RW 25W Lamp(s) 4-FT RW 28W Lamp(s) 4-FT 32W Lamp(s) 8-FT 59W Lamp(s) 8-FT HO 86W Lamp(s)
1 16 23 28 24 26 32 62 85*
2 32 46 56 44 50 59 124 160*
3 48 69 89 66 74 88 186  
4 64 92   90 99 114 248 320*
5           148    
6   134   134   175 328  
8           224    
T5
NUMBER OF Lamps per Fixture 2-FT 14W Lamps 2-FT 24W HO Lamps 4-FT 28W Lamps 4-FT 54W HO Lamps
1 18 27* 32 62*
2 34 52* 64 117*
3 52 79* 96 179*
4 68 104* 128 240*
6     192 360*
8     256 468*
HID
Nominal Watts Pulse Start Metal Halide Metal Halide Mercury Vapor HPS
50   72 74 66
60   67    
70   95   95
75     93  
90   99    
100   128* 125 138
140   153    
150   190   188
175 208 215 205  
200 232     250
210   229    
250 288 295 290 295
310       365
315   343    
350 400      
400 456 455 455 465
450 .red 506      
700     780*  
750 818* 850*   835*
1000 1080* 1080* 1075* 1100*
1500   1610*    

* Pictures are recommended

Ready to Make a Change?

 

Get More Info

Head over to Business Types or Public Sector for energy-reducing ideas specific to your organization.

Send an Email

Email us at BusinessEE@ComEd.com or PublicSectorEE@ComEd.com

 

Give Us a Call

Call us at 1-855-433-2700 during normal business hours to speak with a ComEd Energy Efficiency Program representative.

The ComEd Energy Efficiency Program is funded in compliance with state law.

Offers are subject to change.

© Commonwealth Edison Company, 2019. All Rights Reserved.